A split core WiFi current sensor clamps onto an insulated conductor in a live panel and streams V/I/P/E data over WiFi, with no wire cut and no outage. For retrofits, the decision comes down to a few specs: fit, accuracy, connectivity and safe installation.
A split core WiFi current sensor is a current transformer with a hinged ferrite core that clamps an insulated wire and reports V/I/P/E over 2.4 GHz WiFi by Modbus TCP. This guide covers D1C9002-02 specs, the CT comparison and safe installation. Download the Datasheet →
Key Takeaways
Insulated conductors only; 230 V ±20%, 5(100) A, 2% accuracy, V/I/P/E.
4 mA starting (0.04%Ib), 500 mA minimum (5%Ib), 1000 imp/kWh.
WiFi4 (802.11 b/g/n, 2.4 GHz only) plus Bluetooth, Modbus TCP-IP, 115200-8-N-1.
Clamp only insulated wire, never bare conductor or busbar; secure with a cable tie.
A split core WiFi current sensor is a CT whose ferrite core opens on a hinge to clamp an insulated conductor without breaking the circuit, using high-permeability ferrite, mirror-finished faces and a snap-fit latch. It works as a WiFi energy meter with CT and is also called a split core current transformer, clamp-on current sensor, non-invasive current sensor or open-close current sensor. Uses include solar monitoring with a bidirectional current sensor and IoT dashboards using a wireless current transformer.
Need the drawing before you design the mount? Download the Datasheet →
Rated 230 V ±20%, 5(100) A, 50–60 Hz, with published 2% accuracy for energy management, not billing. Single-phase; for three-phase see our three-phase power meter.
Standard accuracy classes for measuring CTs are defined in IEC 61869-2; the 2% figure here is a published device specification, not a stated IEC class. IEC 61869-2.
A Modbus TCP current sensor reports V/I/P/E bidirectionally; sensitivity is 4 mA starting, 500 mA minimum, 1000 imp/kWh.
Parameter | D1C9002-02 Specification |
Product type | Open-close / split-core WiFi current sensor |
Manufacturer | Ivy Metering Co., Ltd (Shanghai) |
Core material | High-permeability ferrite; mirror-finished contact faces |
Measured quantities | Voltage, current, active power, energy (V/I/P/E), bidirectional |
Voltage input | 230 V (±20%) |
Current range | 5(100) A |
Frequency | 50–60 Hz |
Measurement accuracy | 2% |
Starting current | 0.04%Ib (4 mA) |
Minimum current | 5%Ib (500 mA) |
Pulse constant | 1000 imp/kWh |
Cable aperture | ≤φ12 mm |
Connectivity | WiFi4 802.11 b/g/n, 2.4 GHz only; Bluetooth |
Protocol | Modbus TCP-IP |
Default serial settings | 115200-8-N-1 |
LED status | Flashing: no WiFi / no server connection; solid: connected to server |
Housing | Flame-retardant nylon; epoxy-potted and sealed |
Voltage lead length | 150 ±5 mm |
Operating temperature | -20 to +60 °C |
Warranty | 18-month limited warranty |
Source: D1C9002-02 specification sheet V1.0, Ivy Metering Co., Ltd.
A solid-core CT has no air gap and higher accuracy, but must be threaded onto the conductor, usually de-energizing it. A Rogowski coil has no core and does not saturate, but needs an integrator and separate voltage reference. A non-invasive current sensor in split-core form wins on retrofit speed: open, clamp, snap shut, secure. The trade-off is a joint-dependent 2% class and the ≤φ12 mm aperture.
Criterion | Split-Core (e.g. D1C9002-02) | Solid-Core CT | Rogowski Coil |
Installation | Clamp on live insulated conductor; no shutdown | Must thread conductor; usually requires de-energizing | Wrap around conductor; no shutdown |
Typical accuracy | ~2% class (joint-dependent) | Highest; revenue/protection classes available | Good linearity; accuracy depends on integrator |
Measures voltage & energy directly | Yes — V/I/P/E in one device | No; CT only | No; needs separate voltage/input circuitry |
Low-current sensitivity | 4 mA starting, 500 mA minimum | Good at rated load | Weaker at very low currents |
Saturation risk | Low within rated 100 A | Can saturate at overcurrent | Very low; coreless by design |
Relocation / reuse | Reusable via hinge and latch | Permanent once installed | Reusable |
Built-in connectivity | WiFi4 + Bluetooth, Modbus TCP | Rarely integrated | Rarely integrated |
Best fit | Retrofit, submetering, solar, IoT dashboards | Revenue metering, protection | High-current, wide-dynamic-range measurement |
Choose solid-core for billing-grade accuracy, Rogowski for very high currents, and a split core WiFi current sensor for dependable data from a live system.
Weighing sensor type against your panel constraints? Talk to an Engineer → with your conductor size and accuracy needs.
WiFi4 / 802.11 b/g/n, 2.4 GHz only, no 5 GHz; better penetration but congestion, so verify your SSID supports 2.4 GHz.
Modbus TCP-IP, open and documented by the Modbus Organization, so a PLC, Modbus TCP gateway, SCADA or IoT collector polls V/I/P/E without a proprietary library.
Default 115200-8-N-1; record it, since a mismatch is the most common first-power-up failure.
LED: flashing means no WiFi or server connection; solid means connected.
De-energize where required and follow local codes and PPE; confirm the insulated wire fits ≤φ12 mm; open the latch and place the core around the insulated conductor only, never bare wire or a bare busbar; close the latch fully so the ferrite faces meet; secure the body with a cable tie so it cannot sway; connect the 150 ±5 mm lead; join 2.4 GHz WiFi until the LED turns solid; verify against a known load. Avoid corrosive gases; stay within -20 to +60 °C. See the full installation guide.
Confirm 2% suits the application (not billing), 5(100) A covers peaks, and 4 mA / 500 mA thresholds catch your loads. Verify Modbus TCP-IP support, the register map and 2.4 GHz capacity. Check the 18-month warranty, returns and spares. Measure the insulated conductor diameter first, since an oversized feeder will not close in a ≤φ12 mm aperture.
Ready to specify? Request a Quote → with quantity, voltage and accuracy requirements.
Split-core vs solid-core CT?A solid-core CT has a closed ring and must be threaded onto a conductor, usually requiring de-energizing; a split-core opens on a hinge and clamps an insulated conductor without cutting it. Mirror-finished faces and a tight latch minimize the joint.
Can a split core WiFi current sensor measure bidirectional power, and is 2% accurate enough?Yes: positive and negative current and power distinguish grid import from solar or battery export. ±2% suits energy management and submetering, not revenue billing; also check 4 mA and 500 mA thresholds.
A split core WiFi current sensor adds trustworthy data to a system already running. The D1C9002-02 combines high-permeability ferrite, mirror-finished faces, an epoxy-sealed body, a hinged snap-fit clamp, 230 V ±20% and 5(100) A inputs, 2% accuracy, a 4 mA starting current and bidirectional V/I/P/E, plus 2.4 GHz WiFi4, Bluetooth and Modbus TCP-IP. Three filters: match accuracy to the application, confirm the 2.4 GHz and Modbus TCP path, and install only on insulated conductor with the latch closed and body secured.
Request a Quote → or Download the Datasheet → for your next design review.
{"@context":"https://schema.org","@type":"TechArticle","headline":"Split Core WiFi Current Sensor Guide (D1C9002-02)","description":"230V, 5(100)A, 2% accuracy, Modbus TCP, 4 mA start.","datePublished":"2026-11-20","author":{"@type":"Organization","name":"Ivy Metering"},"publisher":{"@type":"Organization","name":"Ivy Metering"},"mainEntityOfPage":"https://www.ivymetering.com/blog/split-core-wifi-current-sensor-guide"}
{"@context":"https://schema.org","@type":"Product","name":"D1C9002-02 Split-core WiFi Current Sensor","sku":"D1C9002-02","brand":{"@type":"Brand","name":"Ivy Metering"},"description":"Split-core WiFi CT measuring V/I/P/E, Modbus TCP-IP, 2.4 GHz.","additionalProperty":[{"@type":"PropertyValue","name":"Accuracy","value":"2%"},{"@type":"PropertyValue","name":"Current range","value":"5(100) A"},{"@type":"PropertyValue","name":"Voltage input","value":"230 V ±20%"},{"@type":"PropertyValue","name":"Starting current","value":"4 mA (0.04%Ib)"},{"@type":"PropertyValue","name":"Protocol","value":"Modbus TCP-IP"}]}