MD0630T01A-R EMC RS485 RJ12 Socket Residual Current Monitor Solar EVSE RCM Sensor AC 30mA DC 6mA

MD0630T01A-R is an ACDC leakage sensor RCD with RJ12 Output for photovoltaic. The advantages compared with normal fault current detection sensor, it supports the function of digital output function, can read DC and AC current values, and has the characteristics of high sensitivity, plastic shell, SIP package, integrated design, small size, and accurate measurement. current DC current range 2mA to 15mA, AC current 3mA to 100mA, accuracy DC±0.2mA, AC±0.3mA@25℃. The default threshold is DC 6mA, AC 30mA, and the alarm value can be set. UART serial communication, Modbus protocol, It also meets with EN 61000-6-3:2007+A1, EN IEC 61000-6-1:2019 standards, with TUV, CE-EMC certification.


Product Details

Product Features 

Type B Current Detection,Digital Signal (push-pull output)

DC Current:2~15mA; AC current:3~100mA

Default threshold: DC 6mA, AC 30mA , Alarm Value Settable                                         

High Precision, DC ±0.2mA,AC ±0.3mA @25℃                                                          

UART Communication with Modbus Protocol


Product Parameters 

Voltage Input

12V±20%   (Current about 12mA)

Measurement Current Range

DC  current:2~15mA; Max.AC current:3~100mA

(Default threshold: DC 6mA, AC 30mA)

Accuracy

DC±0,2mA,AC±0.3mA@25℃

Three-ways output

DC alarm, AC alarm, AC/DC alarm

Function

Current value readable and settable

Operation temperature

-25~+80℃

Appearance

Plastic casing ,SIP encapsulation

Installation

6 Pin, RJ12 Output


Product Dimension

image.png

Product Application

The generation of MD0630T01A-R leakage current sensors can enable the electrical safety of photovoltaic or solar system. Even it’s quite small but it can play a big role in circuit when fault current occurs. The alarming value can be set into DC6mA 10mA. AC 10mA 15mA 20mA, 30mA etc. In this case the safety of solar panels or solar users can be ensured. What is an RCD? They are devices installed within an electrical system unit to provide protection to the wiring, fixed appliances and persons using the installation. Protection is achieved by constantly monitoring the electric current flowing through one or more circuits that an RCD is used to protect.