MD0630T41A is an automotive grade leakage current sensor also called residual current monitoring (RCM), residual current detection (RCD), differential current sensor, leakage current detector and fault current sensor. It has the characteristics of accurate measurement, small size and integration. The RCD sensor can be set separately for AC and DC leakage and has a digital output function. It can detect sinusoidal AC, pulsating DC, composite of multi-frequency as well as smooth DC residual currents. Widely used for electro-medical instruments, ventilation systems, inverters, UPS, Electric vehicle charging stations, lifts, escalators, welding equipment, smart home, industrial machines, elevators, IOT, photovoltaic systems. In addition, our delivery time is also guaranteed.
Product Description
Any electrical leak can be dangerous for your staff and production site. By using IVY Residual Current Device (RCD) you can protect both staff and equipment. Thanks to its zero-flux technology expertise, IVY developed a range of highly flexible Residual Current Monitor of Type B/B+ for measuring DC and AC residual currents up to 100kHz, with digital signal output.
MD0630T41A sensor is a new, compact, horizontal type rcd current sensor with pins designed for use in e-mobility infrastructure and AC charging station designs to monitor leakage currents in mode two/three/four electric vehicle charging.
MD0630T41A Type A, B and B+ RCD, dedicated to detect to DC, AC and DC+AC leakage current measurement. The sensor can issues an alarm signal when the DC component of the residual current reaches a preset value.
MD0630T41A is a DC/AC leakage current sensor with high sensitivity, accurate measurement, small size, integration, digital output, UART communication, Modbus protocol, etc. The measurement DC current range is 2~15mA, the AC current range is 3~100mA, Type B detection is worth to be mentioned too.
The pin & cable dual installation methods can be used to set AC and DC leakage respectively. When the set current is reached, an alarm signal can be generated. The alarm value is programmable. Three-way output DC alarm, AC alarm, and AC and DC alarm. At the same time, the leakage sensor has a digital output function, which can read the current value of DC and AC, in line with TUV-IEC62955, CE-EMC standards.
Product Features
1. Fixed 6mA DC and 30mA AC trip levels; 3000A surge withstand capability; "Fault” output – Open collector
2. Small Size, Integration Design, Vertical(Pin, Pin&Cable Type)/Horizontal(Cable Type) Mounting Optional
3. Integrated self-monitoring and test functions, Digital Output, Residual Fault Leakage Current Protection
4. AC DC Leakage Data Readable; Alarm Value Programmable; 3 Way Alarm Outputs
5. UART Comm, with Modbus Protocol; Standard: EN 61000-6-3:2007+A1 ,EN IEC 61000-6-1:2019
6. Professional Certification: TUV(IEC62955/IEC62752/IEC61851-1/IEC62196); UL 2231-1/UL 2231-2; CE-EMC
7. Used in EV Charger Project (Full load current up to 80 A r.m.s. (1-phase) or 3 x 32 A r.m.s. (3-phase))
1.Being able to detect smooth DC residual currents which can occur in EV charger stations and photovoltaic systems, IVY RCD guarantees the safety of the people and of the installation
2.can guarantee dependable protection for field technicians and installed machinery by detecting high frequency residual current and protecting against smooth DC residual currents in the event of a fault.
3.can prevent damage to installed equipment and avoid operational impacts in situations where service interruption and out of order can cause discomfort.
4.In installation where we cannot necessarily withstand any sort of interruption, IVY RCD can minimize outages, equipment damage, failures and interruption of any critical operation
Product Parameters
Voltage Input | 12V±20% (Current about 12mA) |
Measurement Current Range | DC current:2~15mA ; Max.AC current:3~100mA (Default threshold:DC 6mA, AC 30mA) |
Accuracy | DC±0,2mA,AC±0.3mA@25℃ |
Three-ways output | DC alarm, AC alarm, AC/DC alarm |
Function | Current value readable and settable |
Operation temperature | -25~+80℃ |
Appearance | |
Installation | PCB+Cable/Pin+Cable/Vertical Installation |
Product Dimension